ABB Drives ACS350 Technical Specifications
Now obsolete - please see the ACS355 - Now obsolete - please see the ACS355
Mains Connection |
|
| Voltage and Power Range | 1 phase, 200 to 240V ± 10% |
| 0.37 to 2.2 kW (0.5 to 3 hp) | |
| 3-phase, 200 to 240 V ± 10% | |
| 0.37 to 4 kW (0.5 to 5 hp) | |
| 3-phase, 380 to 480 V ± 10% | |
| 0.37 to 7.5kW (0.5 to 10 hp) | |
| Frequency | 48 to 63Hz |
| Power factor | 0.98 |
Motor Connection |
|
| Voltage | 3-phase, from 0 to Usupply |
| Frequency | 0 to 500 Hz |
| Continuous loading capability | Rated output current I2N |
| (constant torque at a max. ambient temperature 40oC) | |
| Overload capability (at a max. ambient temperature of 40oC) |
At heavy duty use 1.5 x I2N
for 1 minute every 10 minutes At start 1.8 x I2N for 2 s |
| Switching frequency Default Selectable |
4kHz 4 to 12 kHz with 4 kHz steps |
| Acceleration time | 0.1 to 1800 s |
| Deceleration time | 0.1 to 1800 s |
| Braking | Inbuilt brake chopper as standard |
Environmental Limits |
|
| Ambient temperature | -10 to 40oC (14 to 104oF), no frost allowed, 50oC (122oF) with 10% derating |
| Altitude Output current |
Rated current available at 0 to
1000m (0 to 3281 ft) reduced by 1% per 100m (328 ft) over 1000 to 2000m (3281 to 6562 ft) |
| Relative humidity | Lower than 95% (without condensation) |
| Protection class | IP20 / Optional NEMA 1 enclosure |
| Enclosure colour | NCS 1502-Y, RAL 9002, PMS 420C |
| Contamination levels | IEC721-3-3 |
| No conductive dust allowed | |
| Transportation | Class 1C2 (chemical gases) |
| Class 1S2 (solid particles) | |
| Storage | Class 2C2 (chemical gases) |
| Class 2S2 (solid particles) | |
| Operation | Class 3C2 (chemical gases) |
| Class 3S2 (solid particles) | |
Chokes |
|
| AC input chokes | External option. |
| For reducing THD in partial loads and to comply with EN61000-3-2. | |
| AC output chokes | External option. To achieve longer motor cables. |
Programmable Control Connections |
|
| Two analogue inputs | |
| Voltage signal : Unipolar | 0 (2) to 10 V, Rin > 312kΩ |
| Bipolar | -10 to 10 V, Rin >312kΩ |
| Current signal : Unipolar | 0 (4) to 20 mA, Rin = 100Ω |
| Bipolar | -20 to 20 mA, Rin = 100Ω |
| Potentiometer reference value | 10 V ± 1%, 10mA, R < 10 10Ω |
| Resolution | 0.1% |
| Accuracy | ± 1% |
| On analogue output | 0 (4) to 20 mA, load < 500Ω |
| Auxiliary Voltage | 24 V DC ± 10%, max. 200mA |
| Five digital inputs | 12 to 24 V DC with internal or external supply, PNP and NPN, pulse train 0 to 16kHz. |
| Input impedance | 2.4kΩ |
| One relay output | |
| Type | NO + NC |
| Maximum switching voltage | 250 V AC / 30 V DC |
| Maximum switching current | 0.5 A/30 V DC; 5 A/230 V AC |
| Maximum continuous current | 2 A rms |
| One digital output | |
| Type | Transister output |
| Maximum switching voltage | 30 V DC |
| Maximum switching current | 100 mA / 30 V DC, short circuit protected |
| Frequency | 10 Hz to 16 kHz |
| Resolution | 1 Hz |
| Accuracy | 0.2% |
Product Compliance |
| Low voltage Directive 73/23/EEC with supplements |
| Machinery directive 98/37/EC |
| EMC Directive 89/336/EEC with supplements |
| Quality assurance system ISO 9001 |
| Environmental systems ISO 14001 |
| UL, cUL, CE, C-Tick, and GOST R approvals |
Serial Communication |
|
| Fieldbuses | Plug-in type |
| Refresh rate | < 10 ms (between drive and fieldbus module) |
| PROFIBUS DP | 9 pin D-connector |
| Baud rate up to 12 Mbit / s | |
| PROFIBUS DP and PROFIBUS DPV1 | |
| Network side based on PROFIdrive | |
| DeviceNet | 5-pin D-connector |
| Baud rate up to 12 Mbit/s | |
| PROFIBUS DP and PROFIBUS DPV1 | |
| Network side based on "PROFIdrive" profile | |
| CANopen | 9-pin D-connector |
| Baud rate up to 500 kbit/s | |
| Network side based on CiA DS402 profile | |
| Modbus | 4-pin screw type connector |
| Baud rate up to 115kbit / s | |
EMC (according to EN61800-3) |
| 2nd environmental filter, unrestricted distribution with 30m (98ft) cable inbuilt as standard |
Now obsolete - please see the ACS355 - Now obsolete - please see the ACS355