Mains Connection

Voltage and Power Range 1 phase, 200 to 240V ± 10%
  0.37 to 2.2 kW (0.5 to 3 hp)
  3-phase, 200 to 240 V ± 10%
  0.37 to 4 kW (0.5 to 5 hp)
  3-phase, 380 to 480 V ± 10%
  0.37 to 7.5kW (0.5 to 10 hp)
Frequency 48 to 63Hz
Power factor 0.98

Motor Connection

Voltage 3-phase, from 0 to Usupply
Frequency 0 to 500 Hz
Continuous loading capability Rated output current I2N
(constant torque at a max. ambient temperature 40oC)
Overload capability
(at a max. ambient temperature of 40oC)
At heavy duty use 1.5 x I2N for 1 minute every 10 minutes
At start 1.8 x I2N for 2 s
Switching frequency
Default
Selectable

4kHz
4 to 12 kHz with 4 kHz steps
Acceleration time 0.1 to 1800 s
Deceleration time 0.1 to 1800 s
Braking Inbuilt brake chopper as standard

Environmental Limits

Ambient temperature -10 to 40oC (14 to 104oF), no frost allowed, 50oC (122oF) with 10% derating
Altitude
Output current
 
Rated current available at 0 to 1000m
(0 to 3281 ft) reduced by 1% per 100m
(328 ft) over 1000 to 2000m (3281 to 6562 ft)
Relative humidity Lower than 95% (without condensation)
Protection class IP20 / Optional NEMA 1 enclosure
Enclosure colour NCS 1502-Y, RAL 9002, PMS 420C
Contamination levels IEC721-3-3
  No conductive dust allowed
Transportation Class 1C2 (chemical gases)
  Class 1S2 (solid particles)
Storage Class 2C2 (chemical gases)
  Class 2S2 (solid particles)
Operation Class 3C2 (chemical gases)
  Class 3S2 (solid particles)

Chokes

AC input chokes External option.
  For reducing THD in partial loads and to comply with EN61000-3-2.
AC output chokes External option.
To achieve longer motor cables.

Programmable Control Connections

Two analogue inputs  
Voltage signal : Unipolar 0 (2) to 10 V, Rin > 312kΩ
                          Bipolar -10 to 10 V, Rin >312kΩ
Current signal : Unipolar 0 (4) to 20 mA, Rin = 100Ω
                         Bipolar -20 to 20 mA, Rin = 100Ω
Potentiometer reference value 10 V ± 1%, 10mA, R < 10 10Ω
Resolution 0.1%
Accuracy ± 1%
On analogue output 0 (4) to 20 mA, load < 500Ω
Auxiliary Voltage 24 V DC ± 10%, max. 200mA
Five digital inputs 12 to 24 V DC with internal or external supply, PNP and NPN, pulse train 0 to 16kHz.
Input impedance 2.4kΩ
One relay output  
Type NO + NC
Maximum switching voltage 250 V AC / 30 V DC
Maximum switching current 0.5 A/30 V DC; 5 A/230 V AC
Maximum continuous current 2 A rms
One digital output  
Type Transister output
Maximum switching voltage 30 V DC
Maximum switching current 100 mA / 30 V DC, short circuit protected
Frequency 10 Hz to 16 kHz
Resolution 1 Hz
Accuracy 0.2%

Product Compliance

Low voltage Directive 73/23/EEC with supplements
Machinery directive 98/37/EC
EMC Directive 89/336/EEC with supplements
Quality assurance system ISO 9001
Environmental systems ISO 14001
UL, cUL, CE, C-Tick, and GOST R approvals

Serial Communication

Fieldbuses Plug-in type
Refresh rate < 10 ms (between drive and fieldbus module)
PROFIBUS DP 9 pin D-connector
  Baud rate up to 12 Mbit / s
  PROFIBUS DP and PROFIBUS DPV1
  Network side based on PROFIdrive
DeviceNet 5-pin D-connector
  Baud rate up to 12 Mbit/s
  PROFIBUS DP and PROFIBUS DPV1
  Network side based on "PROFIdrive" profile
CANopen 9-pin D-connector
  Baud rate up to 500 kbit/s
  Network side based on CiA DS402 profile
Modbus 4-pin screw type connector
  Baud rate up to 115kbit / s

EMC (according to EN61800-3)

2nd environmental filter, unrestricted distribution with 30m (98ft) cable inbuilt as standard