ABB ACS550 - Technical Specifications
|
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Mains Connection |
|
| Voltage and power range | 3-phase, 380 to 480 V, +10/-15%, 0.75 - 355 kW 3-phase, 200 to 240 V, +10/-15%, 0.75 - 75 kW Auto-identification of input line |
| Frequency | 48 to 63 Hz |
| Power factor | 0.98 |
Motor Connection |
|||||||||
| Voltage | 3-phase, from 0 to USUPPLY | ||||||||
| Frequency | 0 to 500 Hz | ||||||||
| Continuous loading capability (constant torque at a max ambient temperature of 40oC) |
Rated output current I2 | ||||||||
| Overload capacity (at a max. ambient temperature of 40oC) |
At normal use 1.1 x I2N
for 1 minute every 10 minutes At heavy use 1.5 x I2hd for 1 minute every 10 minutes Always 1.8 x I2hd for 2 seconds every 60 seconds |
||||||||
| Switching frequency Standard Selectable |
|
||||||||
| Acceleration time | 0.1 to 1800 s | ||||||||
| Deceleration time | 0.1 to 1800 s | ||||||||
| Speed control Static accuracy Dynamic accuracy |
20% of motor nominal slip < 1% s with 100% torque step |
||||||||
| Torque Control Torque step rise time Non-linearity |
<10 ms with nominal torque ± 5% with nominal torque |
||||||||
Environmental Limits |
|||||||||
| Ambient temperature -15 to 40oC 40 to 50oC |
No frost allowed fswitch 4 kHz, derating please contact us |
||||||||
| Altitude Output current |
Rated current available at 0 to 1000 m reduced by 1% per 100 m over 1000 m to 2000 m. |
||||||||
| Relative humidity | Lower that 95% (without condensation) | ||||||||
| Protection class | IP 21 or IP 54 | ||||||||
| Enclosure colour | NCS 1502-Y, RAL 9002, PMS 420 C | ||||||||
| Contamination levels Transportation Storage Operation |
IEC 721-3-3 No conductive dust allowed Class 1C2 (chemical gases) Class 1S2 (solid particles) Class 2C2 (chemical gases) Class 2S2 (solid particles) Class 3C2 (chemical gases) Class 3S2 (solid particles) |
||||||||
Programmable Control Connections |
|||||||||
| Two analogue inputs Voltage signal Current signal Potentiometer reference value Maximum delay Resolution Accuracy |
0 (2) to 10 V, Rin > 312 kΩ single ended 0 (4) to 20 mA, Rin = 100Ω single ended 10 V ±2% max. 10 mA, R < 10 kΩ 12 ... 32 ms 0.1% ± 1% |
||||||||
| Two analogue outputs | 0 (4) to 20 mA, load < 500 Ω | ||||||||
| Auxiliary voltage | 24 V DC ±10%, max. 250 mA | ||||||||
| Six digital inputs Input impedance Maximum delay |
12 V .. 24 V DC with internal or external supply, PNP
and NPN 2.4 k Ω 5 ms ± 1ms |
||||||||
| Three relay outputs Maximum switching voltage Maximum switching current Maximum continuous current |
250 V AC / 30 V DC 6 A / 30 V DC; 1500 V A / 230 V AC 2 A rms |
||||||||
| Serial communication RS 485 |
Modbus protocol |
||||||||
Protection Limits |
|||||||||
| Overvoltage trip limits Running V DC Start inhibit DC |
842 (corr. to 595 V input) 661 (corr to 380 - 415 V input) 765 (corr. to 440 - 480 V input) |
||||||||
| Undervoltage trip limits Running V DC |
333 (corr. to 247 V input) 436 (corr. to 380 - 415 V input) 505 (corr. to 440 - 480 V input) |
||||||||
Product Compliance |
|||||||||
| Low Voltage Directive 73 / 23 / EEC with supplements | |||||||||
| Machinery Directive 98 / 37 / EC | |||||||||
| EMC Directive 89 / 336 / EEC with supplements | |||||||||
| Quality assurance system ISO 9001 and environmental system ISO 14001 CE, UL and cUL approvals | |||||||||
EMC (according to EN61800-3) |
|||||||||
| 1st environment restricted
distribution for frame sizes R3, R4 with 30 m motor cables
and for frame sizes R1, R2, R5, R6 with 100 m motor cables 2nd environment unrestricted distribution with 100 m cable as standard For longer motor cable lengths, external EMC filters are available on request |
|||||||||
|
CSE Industrial Electrical Distributors; Email :
- Tel:01628 529448; Fax:01628
810093;
|