ABB Manual Motor Starts

ABB Manual Motor Starters

We hold stocks of Contactors, Thermal overload relays, Manual Motor Starters, Soft starters, Inverters and Control devices such as lamps and pushbuttons. CSE have been distributing ASEA and Brown Boveri products since 1971 and have unrivalled experience in the range of products now offered in the UK.

Manual motor starter type MS116

Manual motor starters from ABB switch motors ON and OFF properly and protect them in case of overload and short circuit. The range covers motors with nominal current from 0,1A up to 100A.

If you are a Schiele customer, follow the link to an Excel conversion table.

Open design, enclosure IP 20 resistant to changeable climates.  Quick fastening on mounting rails DIN EN 50 022, 35mm without auxiliary switch.

Click to buy the ABB Manual Motor Starters on-line.

MS 116 with thermal and electromagnetic trips, short circuit proof up to 50 kA

Rated Power Setting Range Type Order No. Short Circuit breaking Capacity Rated Instantaneous
400 V AC-3
kW
A... A     Ics at 400 V AC
kA
short circuit setting
A
0.03 0.10 ... 0.16 MS116-0.16 1SAM 250 000 R 1001 50 1.25 ... 1.87
0.06 0.16 ... 0.25 MS116-0.25 1SAM 250 000 R 1002 50 1.95 ... 2.92
0.09 0.25 ... 0.40 MS116-0.4 1SAM 250 000 R 1003 50 3.12 ... 4.68
0.12 0.40 ... 0.63 MS116-0.63 1SAM 250 000 R 1004 50 4.91 ... 7.37
0.25 0.63 ... 1.00 MS116-1.0 1SAM 250 000 R 1005 50 9.20 ... 13.8
0.55 1.00 ... 1.60 MS116-1.6 1SAM 250 000 R 1006 50 14.7 ... 22.1
0.75 1.60 ... 2.50 MS116-2.5 1SAM 250 000 R 1007 50 23.0 ... 34.5
1.5 2.50 ... 4.00 MS116-4 1SAM 250 000 R 1008 50 40.0 ... 60.0
2.2 4.00 ... 6.30 MS116-6.3 1SAM 250 000 R 1009 50 63.0 ... 94.5
4 6.30 ... 10.00 MS116-10 1SAM 250 000 R 1010 50 120 ... 180
5.5 10.00 ... 16.00 MS116-16 1SAM 250 000 R 1011 16 192 ... 288
7.5 8.00 ... 12.0 MS116-12 1SAM 250 000 R1012 25 144 ... 216

Technical Data

Standards Conformity to standards    

IEC / EN60947-1, IEC/EN60947-2, IEC/EN60947-4-1, UL 508, CSA C22.2 No. 14

  Phase loss sensitivity (acc. to IEC / EN 60947-4-1) Yes
  Disconnecting feature (acc. to IEC / EN 60947-2) Yes
General Data Mounting position     Position 1-6
  Degree of Protection (acc. to IEC 60947-1) IP20
  Mechanical Durability     100000 cycles
  Electrical Durability     100000 cycles
  Utilisation Category     A
IEC Rated Operational Voltage Ue    
Main Circuit Rated Operational voltage Ue   690 V AC
  Rated Frequency     50 / 60Hz
  Trip Class     10A
Isolation Data Rated impulse withstand voltage Uimp   6kV
(acc. to IEC / EN 60947-1) Rated insulation voltage Ui   690 V
Environmental Data Ambient Air Temperature    
  Operation Open - Compensated -25 ... +55oC
    Open   -25 ... +70oC
    Enclosed (IB132)   0 ... +40oC
  Storage     -50 ... +80oC
  Vibration (acc. to IEC / EN 60068-2-6) 5 g / 3-150Hz
  Shock (acc. to IEC/EN 60068-2-27) 25g / 11 ms
Connecting Capacity Rigid   1 or 2 x 1 ... 4 mm2
Flexible with ferrule   1 or 2 x 0.75 ... 2.5mm2
  Flexible without ferrule   1 or 2 x 0.75 ... 2.5mm2
  Stripping length     9mm
  Tightening torque     0.8 ... 1.2Nm
UL / CSA        
Main circuit Max operational voltage   600 V AC
  Short circuit rating 480 V AC 0.16AIe 2.5A 30 kA
    600 V AC   5 kA
Connecting Capacity Stranded   1 or 2 x AWG 16... 12
Flexible without ferrule 1 or 2 x AWG 16... 12
  Stripping length     9mm
  Tightening torque     10lb. in

Accessories

Type   Order No.
Auxiliary switches, for front panel installation
HKF1-11 1 NO + 1 NC 1SAM 201 901 R 1001
 
Auxiliary switches, lateral attachment at right
HK1-11 1 NO + 1 NC 1SAM 201 902 R 1001
HK1-20 2 NO 1SAM 201 902 R 1002
HK1-02 2 NC 1SAM 201 902 R 1003
 
Signal contact for general "tripped" signal, lateral attachment at right
SK1-11 1 NO + 1 NC 1SAM 201 903 R 1001
SK1-20 2 NO 1SAM 201 903 R 1002
SK1-02 2NC 1SAM 201 903 R 1003
 
Undervoltage release, lateral attachment at left
UA1-24 24V, 50Hz 1SAM 201 904 R 1001
UA1-230 230V, 50Hz 1SAM 201 904 R 1005
 
Undervoltage release with pre-mating auxiliary switch 2S, lateral attachment at left
UA1-HK-24 24V, 50 Hz 1SAM 201 905 R 1001
UA1-HK-230 230V, 50 Hz 1SAM 201 905 R 1005
 
Locking Device
SA1 Lock adapter GJF1 101 903 R 0001
SA3 Locking device assy GJF1 101 903 R 0001
 
Direct Adapter, for wiring to contactors
BEA7 / 116 Mini contactors B6 / B7 1SBN 080 906 R 1000
BEA16 / 116 Contactors A9 / A12 / A16 1SBN 081 406 R 1000
BEA26 / 116 Contactors A26 1SBN 082 406 R 1000
 
Phase Buses for cross wiring MS 116, 63A, 690V
PS1-2-0 for 2 devices without auxiliary switches 1SAM 201 906 R 1002
PS1-3-0 for 3 devices without auxiliary switches 1SAM 201 906 R 1003
PS1-4-0 for 4 devices without auxiliary switches 1SAM 201 906 R 1004
PS1-5-0 for 5 devices without auxiliary switches 1SAM 201 906 R 1005
PS1-2-1 for 2 devices with 1 auxiliary switch 1SAM 201 906 R 1012
PS1-3-1 for 3 devices with 1 auxiliary switch 1SAM 201 906 R 1013
PS1 4-1 for 4 devices with 1 auxiliary switch 1SAM 201 906 R 1014
PS1-5-1 for 5 devices with 1 auxiliary switch 1SAM 201 906 R 1015
PS1-2-2 for 2 devices with 2 auxiliary switches 1SAM 201 906 R 1022
PS1-3-2 for 3 devices with 2 auxiliary switches 1SAM 201 906 R 1023
PS1-4-2 for 4 devices with 2 auxiliary switches 1SAM 201 906 R 1024
PS1-5-2 for 5 devices with 2 auxiliary switches 1SAM 201 906 R 1025
 
Power infeed blocks 63A, 690V, stranded 25mm2, flexible 16mm2
S1-M2 high 1SAM 201 907 R 1002
   
Cover for phase busses
BS1-3 1SAM 201 908 R 1001
 
Switch cubicle mounting kit IP 65, with axial extension triple lockable in Off position, locked in On position
OHY2AJM Twist knob red / yellow 1SCA 022 384 R 7080
OXS5X180 Axis 180mm 1SCA 022 353 R 4620
MSMN Driver*   1SAM 101 923 R 001

*For accommodating spindle and attachment to manual motor starter